100ICS4 - 1" 150RF, 7/32" Orifice, 100 PSI, Float & Thermostatic Trap (L/R)

$3053.54
SKU: D35044
Email a co-worker

More about this product

Armstrong ICS Series Float & Thermostatic steam traps are for industrial service from 0 to 465 psig (32 bar). The simple yet rugged construction of the ICS series carbon steel float and thermostatic trap is designed to assure long, trouble-free service.

The ICS Float and Thermostatic steam trap is used for continuous drainage of condensate and high-capacity venting of air and CO2, when steam pressure may vary from maximum steam supply pressure to vacuum.

Details:

  • Left inlet, right outlet
  • Maximum capacity: 2,750 lb/hr (1,247 kg/hr)
  • Maximum allowable pressure (MAP) : 580 PSIG (40 bar)
  • Maximum operating pressure (MOP) : 100 PSIG (7 bar)
  • Maximum allowable temperature: 650° F (343° C)
  • Connection type: 150RF
  • Connection Size: 1"
  • Orifice Size: 7/32"
  • Steam trap type: Float & thermostatic steam trap
  • Body material: ASTM A352 Grade LCB Carbon Steel