More about this product
The condensate controller (CC) configuration was developed especially to meet very large capacity needs in applications where condensate must be lifted from the drain point to the trap. Under such conditions, often referred to as syphon drainage, the reduction in pressure that occurs when the condensate is elevated causes a portion of the condensate to flash into steam. Ordinary traps, unable to differentiate between flash steam and live steam, close and impede drainage.
Details:
- Equipped with condensate controller
- Maximum capacity: 21,000 lb/hr (9,525 kg/hr)
- Maximum allowable pressure (MAP) : 300 PSIG (21 bar)
- Maximum operating pressure (MOP) : 125 PSIG (9 bar)
- Maximum allowable temperature: 650° F (343° C)
- Connection type: screwed
- Connection Size: 2"
- Orifice Size: 1/2"
- Steam trap type: ultra-capacity float & thermostatic steam trap
- Body material: ASTM A395 ductile iron
-
Product Downloads
-
Manufacturer Info
Armstrong