More about this product
The Fireye E120 Flame-Monitor Control Module is a microprocessor-based burner management system designed to provide safe and reliable sequencing, ignition, and flame monitoring for automatically ignited oil, gas, and combination fuel burners. Operating at 220 VAC, the E120 is a direct counterpart to the E110 model, offering the same advanced features but tailored for international or high-voltage applications.
The E120 supports a wide range of interchangeable programmer modules, flame amplifier modules, and display modules (such as the ED510 or ED500), allowing full customization of control functions and flame detection methods. It is compatible with UV, IR, flame rod, photocell, and self-check UV scanners, depending on the amplifier used.
Details:
- EB701 chassis with EC600 dust cover and 48-1836 mounting screw
- Voltage: 220 VAC (187–242 VAC), 50/60 Hz
- Compatible with UV, IR, flame rod, photocell, self-check UV scanners
- Remote display and reset capability
- Expanded annunciation of safety lockouts
- Non-volatile memory for retaining system status during power loss
- Modbus RS485 communication for integration with building automation systems
- Selectable purge timing and interlock messaging
- Direct interchangeability with Fireye D-Series and C-Series controls
The E120 and EB701 control is not approved by any U.S. approval agencies (Underwriter’s Laboratories, Factory Mutual, Industrial Risk Insurers).
-
Product Download
-
Manufacturer Info
Fireye