Fireye EP382 - 10/15 TFI, 1 Second Purge, Recycle or Non-Recycle
Out of stock
Ships in 1-2 weeks if you order today
More about this product
The EP382 programmer provides start-up programming, safe start check, and flame monitoring supervision. It insures proof of low fire position, and fuel valve end switch safety checks. The control is designed to initiate a safety lockout if any of these circuits are open at the improper point in the control cycle. A running interlock circuit on the Flame-Monitor system constantly monitors the limit switches, air flow switches, and fuel pressure switches through the programmer. A modulator (firing rate motor) circuit is not provided on this Programmer Module.
The programmer module will de-energize all fuel valve circuits within four (4) seconds (max.) following a flame failure or at the end of the pilot trial for ignition period if no flame is detected. An alarm circuit will be energized following a safety lockout.
The programmer module includes an RJ45 style connector to interface with an integral or remote alpha-numeric display (P/N ED510). It is also backward compatible with the ED5001 display. It includes two (2) additional RJ style connectors to connect to an E500 Communication Interface in a multi-drop configuration. The programmer will also communicate with the E500 via the standardED550 cables to provide backward compatibility.
Details:
- For use with the Fireye EB700 and E110 chassis, and ED510 display
- PTFI: 10 seconds
- MTFI: 10/15 seconds
- Flame failure response timing (F.F.R.T) : 4 seconds
- Purge timing: 1 second
- Purge timings can be increased
- Recycle or non-recycle running interlocks
-
Product Downloads
-
Manufacturer Info
Fireye
Related Items
-
- In Stock:
- 3 available
Ships today if you order within 3 hrs 41 mins Ships tomorrow
-
- In Stock:
- 4 available
Ships today if you order within 3 hrs 41 mins Ships tomorrow
-
- In Stock:
- 1 available
Ships today if you order within 3 hrs 41 mins Ships tomorrow