The Fireye BurnerLogix™ System is a microprocessor based burner management control system designed to provide the proper burner sequencing, ignition and flame monitoring protection on automatically ignited oil, gas, and combination fuel burners.

Details:

  • A consistent flame signal read-out via display module or 4-20 mA output
  • Read-out of main fuel operational hours and complete cycles via display module
  • Modbus communications via RS485 multi-drop link
  • Proof of fuel valve closure during off cycle
  • Burn-in time of program parameters occurs after 8 hours of main valve on time
  • A run/check switch which allows the operator to stop the program sequence in any of four different positions (Purge, PTFI, MTFI or Auto)
  • Remote display mounting with NEMA 4 protection
  • Remote reset
  • Revert to pilot can increase burner turn down