More about this product
Details:
- Fan and limit controller
- Fan switch makes and high limit switch breaks on temperature rise
- 25 degree high limit differential
- Used with forced warm air heating systems
- Surface or universal mounting bracket available
- 8" insertion
- Operating temperature range: -40 to 190° F
- Maximum ambient temperature at switch: 190° F
- Maximum ambient temperature at element: 350° F
- 100 to 250° F high limit
- 65 to 215° F for fan-on
- 50 to 250° F for fan-off
-
Product Downloads
-
Manufacturer Info
Honeywell