More about this product
The EP160 programmers provides start-up programming, safe-start check, and flame monitoring supervision. They insure open damper (high-purge) pre-purge, proof of low fire position, and fuel valve end switch safety checks. A running interlock circuit on the FLAME-MONITOR system constantly monitors the limit switches, air flow switches, and fuel pressure switches through the programmer. The programmer control is designed to initiate a safety lockout if any of these circuits are open at the improper point in the control cycle.
Details:
- For use with the Fireye EB700 and E110 chassis, and ED510 display
- PTFI: 10 seconds
- MTFI: 10/15 seconds
- Flame failure response timing (F.F.R.T) : 4 seconds
- Purge timing: 30 seconds
- Purge timings are adjustable
- Non-recycle running interlocks
-
Product Downloads
-
Manufacturer Info
Fireye